Linear heat detection clips fixings come in different variants.
Linear heat cable fixings.
Linesense provide the following selection of fixings and clips to retain the linear heat detection lhd cable in place.
Linear heat detection cable.
Application fixings linear heat detection cable lhdc general guidelines for installation of lhdc.
Fixings should be placed at intervals of no more than 1 2m apart.
Lhdc should not be in contact with any material that can act as a heat sink.
The below drawing represents various clips and fixings that can be used in a typical cable tunnel.
This can be due to either inability to sustain environmental requirements or through prohibitive costs.
The correct size and type of cable gland must be used on all junction box etc.
Lios de tect is a robust linear heat detection system based on optical fibers.
The below drawing represents various clips and fixings that can be used in a typical cable tunnel.
The cable should not be in contact with any material that will act as a heat.
Due to the high impedance of the system all connections at zone monitors eol jb.
Application fixings linear heat detection cable lhdc general guidelines for installation of lhdc.
The taichung power plant is the largest coal fired power plant in taiwan and the third largest in the world.
Patol supply a full range as shown over the page.
Digital lhdc operates at fixed temperatures and is non resettable.
Some 24 000 metres of linear heat detection lhd cable from linesense have been supplied to provide fire protection for one of the world s most important power plants.
Application fixings linear heat detection general guidelines for installation of lhdc.
The correct size and type of cable gland must be used on all junction box etc.
With a range of up to 10 km and a sampling interval down to 25 cm the system is ideal for fire detection in tunnels and metros as well as large facilities like warehouses and industrial facilities.
Patol supply a full range as shown over the page.
Linear heat detection fixings and brackets.
The digital linear heat detection cable comprises of a twisted pair two core cable.
In accordance with bs5389 pt1 2002 lhdc should be spaced no more than 5 3m away from any zone boundary or wall and no more than 10 6m between adjacent runs.
The analogue linear heat detection cable lhdc is designed to provide detection of fire and overheating in circumstances where other forms of detection would not be viable.
Use a suitable clip for whatever you are trying to fix the cable to.
Digital linear heat detection cable.